Item # 4/3FHDFG, Flat Jacketed Heavy Duty Type THW Submersible Pump Cable
Submersible Pump Cable, 600 Volts. UL Certified
Thermoplastic PVC Insulation
MORE IMAGES
Voltage Rating | 600 Volts |
Type | Grounded |
Insulation | Moisture Resistant Thermoplastic PVC |
Industry Standards | UL Certified |
Number Of Insulated Conductors | 4 |
Conductor Size | 4 AWG |
Grounding Conductor Size | 8 AWG |
Copper Content | 428.9 LBS/MFT |
Insulation Thickness/ Minimum PVC | 0.036 in0.914 mm |
Insulation Thickness/ Minimum Nylon | 0.006 in0.152 mm |
Jacket Thickness | 0.060 in1.524 mm |
Cable O.D | 1.47x0.44 in37.3x11.1 mm |
Nominal Cable Weight | 721 LBS/MFT |
Ampacity (30º C Ambient Temperature) | 79 |
Temperature Rating | Dry: 90 °C Wet: 75 °C |
Conductor | Class B , soft drawn, bare copper per ASTM B3 and ASTM B8. |
Insulation | Heat and moisture resistant, polyvinyl chloride meeting the requirements of UL 83 for Type THHN and THWN wires. The insulation is acceptable for use in locations at 90°C dry or 75°C wet. The insulation thickness is in accordance with Table 25.1 of UL 83. |
Conductor Jacket | A nylon jacket is applied directly to the surface of the PVC insulation. Nylon shall meet the requirements of UL 83. The thickness is in accordance with Table 25.1 of UL 83 |
Ground Conductor | Class C (19 strand), soft drawn, bare copper per ASTM B3 and ASTM B8. The conductor is insulated with PVC/'Nylon and the nominal overall diameter shall equal the insulated circuit conductors. |
Assembly | The insulated circuit and grounding conductors are laid flat and parallel together. The jacket will be applied directly over the insulated conductors encapsulating them. |
Jacket | Heat and moisture resistant black polyvinyl chloride meeting the requirements of UL 83. The thickness is in accordance with Table 25.5 of UL 83. |
Color Code | Black, yellow, red & green grounding conductor |
Surface Marking | The overall jacket will have the following information printed: SUBMERSIBLE PUMP CABLE NUMBER AND SIZE OF CONDUCTORS, THHN OR THWN CDRS 75°C WET 600 V(UL) |
600 volt, submersible pump cable with polyvinyl chloride (PVC) insulated and nylon jacketed circuit and grounding conductors, with an overall polyvinyl chloride (PVC) jacket. The cable is suitable for use within well casings for wiring deep well Fresh or salt water submersible pumps. Also for agriculture, farming and livestock where supplying water is needed.