Item # 2/0-3FHDFG, Flat Jacketed Heavy Duty Type THW Submersible Pump Cable

Length:
*
Notes:
Qty:

Item # 2/0-3FHDFG, Flat Jacketed Heavy Duty Type THW Submersible Pump Cable

Submersible Pump Cable, 600 Volts. UL Certified
Thermoplastic PVC Insulation

MORE IMAGES

Voltage Rating 600 Volts
Type Grounded
Insulation Moisture Resistant Thermoplastic PVC
Industry Standards UL Certified
Number Of Insulated Conductors 4
Conductor Size 2/0 AWG
Grounding Conductor Size 6 AWG
Copper Content 1313.2 LBS/MFT
Insulation Thickness/ Minimum PVC 0.045 in1.143 mm
Insulation Thickness/ Minimum Nylon 0.007 in0.178 mm
Jacket Thickness 0.060 in1.524 mm
Cable O.D 2.360x0.69 in59.9x17.5 mm
Nominal Cable Weight 2034 LBS/MFT
Ampacity (30º C Ambient Temperature) 166
Temperature Rating Dry: 90 °C Wet: 75 °C
Conductor Class B , soft drawn, bare copper per ASTM B3 and ASTM B8.
Insulation Heat and moisture resistant, polyvinyl chloride meeting the requirements of UL 83 for Type THHN and THWN wires. The insulation is acceptable for use in locations at 90°C dry or 75°C wet. The insulation thickness is in accordance with Table 25.1 of UL 83.
Conductor Jacket A nylon jacket is applied directly to the surface of the PVC insulation. Nylon shall meet the requirements of UL 83. The thickness is in accordance with Table 25.1 of UL 83
Ground Conductor Class C (19 strand), soft drawn, bare copper per ASTM B3 and ASTM B8. The conductor is insulated with PVC/'Nylon and the nominal overall diameter shall equal the insulated circuit conductors.
Assembly The insulated circuit and grounding conductors are laid flat and parallel together. The jacket will be applied directly over the insulated conductors encapsulating them.
Jacket Heat and moisture resistant black polyvinyl chloride meeting the requirements of UL 83. The thickness is in accordance with Table 25.5 of UL 83.
Color Code Black, yellow, red & green grounding conductor
Surface Marking The overall jacket will have the following information printed: SUBMERSIBLE PUMP CABLE NUMBER AND SIZE OF CONDUCTORS, THHN OR THWN CDRS 75°C WET 600 V(UL)
600 volt, submersible pump cable with polyvinyl chloride (PVC) insulated and nylon jacketed circuit and grounding conductors, with an overall polyvinyl chloride (PVC) jacket. The cable is suitable for use within well casings for wiring deep well Fresh or salt water submersible pumps. Also for agriculture, farming and livestock where supplying water is needed.